Temporary power connection do's and don'ts
Do’s:
- Be sure to pick up a work permit from the person in charge of the site and do a Toolbox Talk.
 - Any electrical work is to be performed by a licensed electrician.
 - All the apparatus should be flameproof.
 - For three-phase power, the equipment shall have double neutral earthing.
 - An earth-leakage circuit breaker must be used in all the apparatuses.
 - All equipment shall have a current rating not exceeding 30 AMPS.
 - Check for the correct rating, Direct Online Motor Starter on each machine.
 - One of the Main power connections should use good-quality armored cable.
 - Should cables be lying in the street, road crossing, or pedestrian areas must be covered and concealed in order to render them resistant to mechanical assaults.
 - Always use non-jointed cables.
 - Cables above ground should be stretched as far as is practicable.
 - At all times, keep connections clean, dry, and tight.
 - Turn off any power supplies to the feeder pillar as soon as the equipment is not in use on a daily basis.
 - If you don’t need temporary power, tell the maintenance person after you have landed the job.
 
Don’ts:
- Never use a power supply higher than 24 V in a cramped area.
 - Unarmored cable shall not be laid down defensively.
 - Twist or carry connections between two wires.
 - Do not site a temporary feeder pillar close to water.
 - Don't sublet a temporary connection to another contractor.
 - Do not apply a load before informing the electrical maintenance department of the use of a temporary electric source.
 - No unauthorized electrician at the job site.
 
Also Read: https://www.linkedin.com/pulse/myths-facts-what-do-you-believe-anshuman-agrawal-mlt-1-
                        We at Minimac study your maintenance needs and provide the best solution. We believe in Discern, Design & Deliver.
                        
                        Call +91 7030901266 for Mechanical Maintenance & Oil Check.
                    
                                